Service Manuals, User Guides, Schematic Diagrams or docs for : . Car Manuals Subaru Legacy 1995-1999 Approved Subaru Legacy 1996 1996 Service Manual MECHANICAL COMPONENTS SECTION AIR CONDITIONING SYSTEM MSA5TCD96L6248

<< Back | Home

Most service manuals and schematics are PDF files, so You will need Adobre Acrobat Reader to view : Acrobat Download Some of the files are DjVu format. Readers and resources available here : DjVu Resources
For the compressed files, most common are zip and rar. Please, extract files with Your favorite compression software ( WinZip, WinRAR ... ) before viewing. If a document has multiple parts, You should download all, before extracting.
Good luck. Repair on Your own risk. Make sure You know what You are doing.




Image preview - the first page of the document
MSA5TCD96L6248


>> Download MSA5TCD96L6248 documenatation <<

Text preview - extract from the document
  SERVICE PROCEDURE                                                4-7
                                              7. Evacuating and Charging


          7. Evacuating and Charging
          The following points should be kept in mind when evacu-
          ating and charging with a manifold gauge set.
          1) Be certain that goggles and gloves are worn.
          2) If bulk refrigerant [13.6 kg (30 lb) canister] is used, be
          certain to weigh the charge amount carefully, using the
          correct equipment, to avoid overcharging the system.
          3) The charging procedure described in this section
          begins by charging liquid refrigerant into the high- pres-
G4M0596   sure side of the system with the engine off. The proce-
          dure is completed by charging refrigerant vapor into the
          low-pressure side of the system with the engine running.
          CAUTION:
          Never open the high-pressure manifold valve when the
          engine is running.




          1. CONNECT THE GAUGE SET
          1) Close the high- and low-pressure manifold valves.
          2) Attach the low-pressure manifold hose to the low- pres-
          sure service port on the vehicle. Check the low- pressure
          gauge. If more than 68.6 kPa (0.70 kg/cm2, 10 psi) is
          indicated, discharge the system prior to charging.
          3) Attach the high-pressure manifold hose to the high-
          pressure service port on the vehicle.
          4) Connect the center hose from the manifold to the
G4M0597   vacuum pump.
          5) Turn on the vacuum pump.
          6) Slowly open the low-pressure manifold valve.
          7) When the low-pressure gauge reaches approximately
          66.43 kPa (498.3 mmHg, 19.62 inHg), slowly open the
          high-pressure manifold valve.




          8) Maintain a minimum vacuum level of 100.56 kPa (754.4
          mmHg, 29.70 inHg) for a minimum of 15 minutes on a new
          system or 30 minutes for an in-service system.
          NOTE:
          The gauge will read 4 kPa (25 mmHg, 1 inHg) less for
          every 304.8 m (1,000 ft) above sea level.



G4M0598




                19
4-7                            SERVICE PROCEDURE
7. Evacuating and Charging


                                       2. PERFORM A VACUUM LEAK TEST
                                       1) After 15 minutes (or more) of evacuation, close the
                                       high-pressure manifold valve.
                                       2) Close the low-pressure manifold valve.
                                       3) Turn off the vacuum pump.




                             G4M0599


                                       4) Note the low side gauge reading.
                                       5) After 5 minutes, re-check the low-pressure gauge read-
                                       ing.
                                       If the vacuum level has changed more than 4 kPa (25
                                       mmHg, 1 inHg), perform an HFC-134a leak test.
                                       If the vacuum reading is about the same as noted in step
                                       2-4), continue on to step 2-6).


                             G4M0600


                                       6) Carefully attach the can tap to the refrigerant can by
                                       following the can tap manufacturer's instructions.
                                       7) Disconnect the center manifold hose from the vacuum
                                       pump and connect the hose to the tap valve.




                             G4M0980


                                       8) If a 13.6 kg (30 lb) container of refrigerant is used a
                                       weight scale will be needed. This scale is to determine the
                                       amount of refrigerant that is used.
                                       Connect the center hose from the manifold to the valve.
                                       Place the 13.6 kg (30 lb) container on the scale, valve end
                                       down.



                             G4M0981

                                       3. PURGE THE CENTER HOSE
                                       1) Verify that all three hose connections are tight at the
                                       manifold gauge set.
                                       2) Open the valve on the HFC-134a source.
                                       3) With safety equipment in place (goggles and
                                       gloves), use extreme caution and loosen the center hose
                                       connection at the manifold and allow the HFC-134a to
                                       escape for no more than two or three seconds, then quickly
                                       retighten the hose fitting at the manifold.
                             G4M0603




                                             20
  SERVICE PROCEDURE                                                4-7
                                              7. Evacuating and Charging


          4. INITIAL CHARGING THROUGH THE HIGH SIDE
          1) Connect a tachometer to the engine.
          2) With the engine off, start charging by slowly opening
          the high-pressure manifold valve.
          NOTE:
          The initial charge rate can be increased by immersing the
          can in lukewarm [Below 38



◦ Jabse Service Manual Search 2026 ◦ Jabse PravopisonTap.bg ◦ Other service manual resources online : FixyaeServiceinfo